Minn. R. 1346.5630 : Labor and Industry Department — MINNESOTA MECHANICAL AND FUEL GAS CODES —MINNESOTA FUEL GAS COD — SECTION 630 (IFGC) INFRARED RADIANT HEATERS

Subpart 1. [Repealed, 34 SR 537]
Subp. 2. [Repealed, 34 SR 537]
Subp. 3. Section 630.

IFGC Section 630 is amended by adding a subsection to read as follows:

630.3 Ventilation air. Where unvented infrared heaters are installed, mechanical ventilation shall be provided to exhaust at least 4 cubic feet per minute (cfm) (0.0203 m 3/s) per 1,000 Btu/hr (0.292 kW) input rating and it shall be electrically interlocked with the heater. Makeup air shall be provided to the space to be heated.

Minn. R. 1346.5630

29 SR 299; L 2007 c 140 art 4 s 61; art 13 s 4; 34 SR 537

Statutory Authority: MS s 16B.59; 16B.61; 16B.64; 326B.101; 326B.106; 326B.13