IFGC section 303.3, Prohibited locations, is amended by deleting items 3 and 4 from the list of exceptions.
Subpart 1.
Section 303.3.
IFGC section 303.3, Prohibited locations, is amended by deleting items 3 and 4 from the list of exceptions.
Subp. 2.
Section 303.3.1.
IFGC section 303.3.1 is amended to read as follows:
303.3.1
Fireplaces and decorative appliances in Group I-1, Condition 2 and Group I-2, Condition 2 occupancies. Direct-vent gas fireplaces shall be permitted inside smoke compartments containing dwelling units, sleeping rooms, and patient sleeping areas where all of the following conditions are met:
1. The direct-vent gas fireplaces are not located within a sleeping room.
2. The direct-vent fireplaces have a sealed glass front with a wire mesh panel or screen.
3. The controls for the direct-vent gas fireplace are located where they can be accessed only by facility staff.
4. Electrically supervised carbon monoxide detection is provided in the room where the direct-vent gas fireplace is located.
5. The direct-vent fireplace includes a guard in front of the glass where the glass temperature is equal to or exceeds 125°F (52°C).
REPEALED, 34 SR 537 39 SR 690; 44 SR 1085
Statutory Authority: MS s 326B.02; 326B.101; 326B.106; 326B.13