(1) The use of any energy conservation measures or method or design or construction not specifically specified under these rules shall not be prevented by the authority having jurisdiction if such energy conservation measures or method or design or construction is found to be satisfactory by the Energy Conservation Building Code Compliant Technical Grievance Redressal Committee and such energy conservation measures or method or design or construction assist the owner in optimizing the energy performance index ratio in the use of energy on its occupancy.
(2) The Code shall be reviewed periodically, at least once in five years, to determine the need for revision or withdrawal of standards specified in the Code, and such standards which in the opinion of the Bureau need no revision or amendment shall be reaffirmed.
Form I
[See Rule 5(1)]
Application for seeking building permit in respect of erection/re-erection/making alteration in the Energy Conservation Building Code compliant Building
To
The Commissioner or (name of the competent authority)
Authority having jurisdiction,
Name of the city
Name of the StateDate: __/__/____
Subject: Application for erection of Energy Conservation Building Code compliant building in premises of Plot no. Block No. Scheme . Street .Name of the town/city
Sir,
I/We the undersigned hereby give you notice of my intention to erect/re-erect/alter Energy Conservation Building Code Compliant Building under the Energy Conservation Building Code Rules, 2018 in the premises of plot No. .Block No. .Scheme .and request for issue of building permit for the construction of the Energy Conservation Building Code compliant building. The following documents are enclosed
(i) Construction Documents and Compliance Forms together with check-lists incorporating the installation of Energy Conservations Measures specified in the aforesaid rules.
(ii) The Construction Documents and Compliance Forms together with check-lists have been verified by Shri .Regd. number .Empanelled Energy Auditors (Building). A certificate in Form II duly signed and sealed in this regard is enclosed.
Yours faithfully,
(Name of the owner)
Address .
Tel. No./Mobile No.
Form II
[See Rule 5(1)(a)]
[Undertaking by owner for construction of the Energy Conservation Building Code compliant building]
I/We am/are the owner(s) of the aforesaid Plot No. Block No. .and the proposed building on completion of construction shall have a connected load/contract demand of 100 kW/120 kVA or above and is proposed to be constructed to use or intended to be used for commercial purposes.
The proposed building accordingly attract the provisions of Energy Conservation Building Code Rules, 2018.
I/we undertake that the aforesaid building shall be constructed in accordance with the bye-laws of the Municipal Authority and the provisions of the Energy Conservation Building Code Rules, 2018. In case any deviation is noticed during the construction of the Building, I/we shall indemnify the loss to the authority having jurisdiction.
I/we further undertake that the information supplied in the enclosed drawings and the application is accurate to the best of my/our knowledge and if any of the information supplied is found to be incorrect and such information result in loss to the Central or the State Government or any other authority under them. I/we undertake to indemnify such loss.
Signature
(Name of the owner)
Address .
Mobile No/Tel No. .
Form III
[See Rule 5(1)(c)(ii) and 5(4)(a)(i)]
[Certificate from Empanelled Energy Auditors (Building) to be enclosed with the application for Building Permit for Energy Conservation Building Code compliant building]
Certificate
I/We am/are Empanelled Energy Auditors (Building) having registration No./ under the Energy Conservation Act, 2001 (52 of 2001) and am authorized to scrutinize and verify the design of Energy Conservation Building Code compliant building. I/We certify that
(a) I/We have scrutinized the construction documents, undertaking given by the owner duly signed by the owner/design professional showing all the pertinent data and features of the building, equipment and systems in sufficient details covering building envelop, heating, ventilation and air-conditioning, service hot water, lighting and electrical power in accordance with municipal bye-laws and with the Energy Conservation Building Code Rules, 2018 in respect of building proposed to be constructed on plot on .block no .scheme in the city of .in the State of .;
(b) I/We have scrutinized the compliance forms with the check-lists to ensure compliance with the bye-laws and the Energy Conservation Building Code Rules, 2018.
(c) The compliance documents have been duly inspected by the undersigned.
(d) The energy performance index ratio of the building design as per compliance documents, at the design stage is equal to or less than one and is therefore in compliance with the Energy Conservation Building Code Rules, 2018.
(e) It is certified that all required scrutiny and verification of the documents submitted have been carried out diligently, truthfully and all reasonable professional skill, care and diligence have been taken in scrutinizing and verifying the drawings of the buildings and compliance forms together with check lists covering the various components of the Energy Conservation Building Code Rules, 2018.
(f) The contents of all the documents submitted along with the application are a true representation of the facts and nothing has been concealed.
There is no objection for issue of building permit in respect of the aforesaid proposed building in so far as requirements of Energy Conservation Building Code Rules, 2018 are concerned.
Signature
Name of the Empanelled Energy Auditors (Building)
Registration No./SEAL
Date
Form IV
[See Rule 5(3)(e)(i) & 5(4)(a)(i)]
[Certificate of Inspection by Empanelled Energy Auditors (Building) on review of Building Permit Application in respect of the proposed building -Communication of omissions and non-compliance to owner]
To
Shri .,
Address
Subject: Application for erection of proposed Building in premises of Plot no. . Block No. . Scheme .Street .Name of the town/city-Details of omission/non-compliance with the Energy Conservation Building Code Rules, 2018 on design stage inspection
Sir,
I/We, .(Name), being an authorised Empanelled Energy Auditors (Building)vide order No. .hereby state I/we have reviewed and verified the undertaking given by you and have inspected the construction documents, compliance forms, check-lists, submitted along with building permit application in respect of the various elements specified in sub-rule (3) of Rule 5 of the various components of the proposed building in respect of the subject building and inform that the following omission/non-compliance have been discovered on inspection
(i)
(ii)
(iii)
(iv)
It is requested that the necessary energy conservation measure in consultation with your design team be carried out in order to bring them in compliance with the Energy Conservation Building Code Rules, 2018. You are accordingly requested to take corrective action within a period of one month from the date of issue of this letter. Further action on your application for issue of building permit shall be taken after satisfactory compliance of the aforesaid omission/non-compliance.
Signature
Empanelled Energy Auditors (Building)
Registration number/Mobile number
Seal
Form V
[See Rule 5(3)(f)]
[Certificate of Inspection by Empanelled Energy Auditors (Building) on review of building permit application enclosing construction documents and compliance forms in respect of Energy Conservation Building Code compliant building]
I/We, .(Name), being an authorised Empanelled Energy Auditors (Building) vide order No. . .hereby state that I/we have reviewed and verified the undertaking given by the owner,, and have inspected the construction documents, compliance forms, check-lists, submitted along with building permit application in respect of the various elements of the proposed Energy Conservation Building Code compliant building in the premises of plot No .Block No. . Scheme .Town/City .State of .and certify that the
(i) the omission/non-compliance pointed out by the undersigned in the certificate of Inspection dated .have been complied with satisfactorily;
(ii) the energy performance index ratio calculation match with the data given in the aforesaid documents and is in compliance with the Energy Conservation Building Code Rules, 2018.
I/We further certify that
(a) all reasonable professional skill, care, and diligence have been taken in verifying the compliance forms in respect of the various elements of the components covered in Energy Conservation Building Code Rules, 2018 and contents thereof are a true representation of the facts and meet the requirements of Energy Conservation Building Code Rules, 2018.
(b) There is no objection for issue of building permit in respect of the aforesaid proposed building in so far as requirements of Energy Conservation Building Code Rules, 2018 are concerned.
The check-list duly completed and signed by the undersigned is enclosed.
Signature
Authorized/Empanelled Energy Auditors (Building)
Registration number/Mobile number
Seal
Form VI
[See Rule 5(5)(a)]
Notice for commencement of construction work of Energy Conservation Building Code compliant building
To
Date: __/__/____
The Commissioner or (name of the competent authority)
Authority having jurisdiction,
Name of the City
Name of the State
Subject: Erection of Energy Conservation Building Code compliant building on premises of Plot no. .Block No. Scheme .Street .Name of the town/city-Notice for commencement of building construction works
Sir,
I/We hereby give notice for commencement of building works including implementation of Energy Conservation Measures for erection of Energy Conservation Building Code compliant building in the aforesaid site i.e. Plot No. scheme street in pursuance of the sanction granted by the Authority having jurisdiction/vide file No./letter No .
Yours faithfully
Signature of the owner
(Name of the owner)
Address of the owner
Form VII
[See Rule 5(4)(b) and (d)]
[Certificate of Inspection by Empanelled Energy Auditors (Building) on review of construction works enclosing construction documents and compliance forms in respect of Energy Conservation Building Code compliant building Issue of certificate of compliance]
To
The Owner,
Address
I/We, .(Name), being an authorised/Empanelled Energy Auditors (Building) vide order No. .hereby state I/we have reviewed the undertaking given by the owner, energy conservation measures installed during the construction works and have reviewed the construction documents, compliance forms, check-lists, submitted along with progress in construction works in respect of the various elements of the components referred to in sub-rule (6) of Rule 5 of the proposed Energy Conservation Building Code compliant building in the premises of plot No. Block No. .scheme .Town/City .State of . and certify that the energy performance index ratio calculation match with the data given in the aforesaid documents;
I/We further certify that all reasonable professional skill, care, and diligence have been taken in verifying the construction document and compliance forms in respect of the various elements of the components covered in Energy Conservation Building Code Rules, 2018 and contents thereof are a true representation of the facts and meet the requirements of Energy Conservation Building Code Rules, 2018.
The check-list duly completed and signed by the undersigned is enclosed.
Signature
Name
Empanelled Energy Auditors (Building)
/Registration No./Mobile number.
Seal
Copy to: Commissioner, Authority having jurisdiction/Name of the City/Town Chief Executive, State designated agency/Name of State/Address
Form VIII
[See Rule 5(6)(c)]
[Certificate of Inspection by Empanelled Energy Auditors (Building) on review of construction works enclosing construction documents and compliance forms in respect of Energy Conservation Building Code compliant building Issue of certificate of non-compliance]
To
Shri
owner
Address
Date: __/__/____
Sub: Erection of Energy Conservation Building Code compliant Building on premises of plot No. .block No. .scheme .street .name of the town/city-Communication of findings by the Empanelled Energy Auditors (Building)
Sir/Madam,
I/We, .(Name), being an authorised/Empanelled Energy Auditors (Building)vide order No. . .hereby state I/we have reviewed the undertaking given by the owner, and energy conservation measures under construction and have reviewed the construction documents, compliance forms, check-lists, submitted along with progress in construction works in respect of the various elements of the components of the proposed Building in the premises of plot No. .Block No. .Scheme .Town/City .State of .and have to state that the construction has not proceeded in accordance with the sanctioned plan and has deviated/is deviating from the following provisions of Energy Conservation Building Code Rules, 2018 namely
(i)
(ii)
(iii)
2. None of the above deviations are covered in the best practices approved by the State Energy Conservation Building Code Implementation Committee.
or
The following deviations are covered in the best practices by the State Energy Conservation Building Code Implementation Committee.
3. The building owner is requested to rectify the above deviations or take the approval of the Energy Conservation Building Code Technical Grievance Redressal Committee.
4. The building owner after obtaining the approval provided in Para 3 above or rectifying the deviations notified in Para 1 above may inform the undersigned of the action taken in the matter within one month from the date of approval obtained or rectification completed along with the updated check-list to enable me to inspect the works in connection with the issue of certificate of approval provided in clause (d) of sub-rule (6) of Rule 5 of the Energy Conservation Building Code Rules, 2018.
Yours faithfully
Signature
Name of
Authorized/
Empanelled Energy Auditors (Building)
number/Mobile number.
Seal
Copy to: Commissioner, Authority having jurisdiction/Name of the City/Town/State
Form IX
[See Rule 5(7)]
Notice of Completion
To
The Commissioner
Authority having jurisdiction
Name of the Town/State
Subject: Construction of Energy Conservation Building Code compliant building on plot No. in block No. .town .Notice of completion of construction of Energy Conservation Building Code compliant works
Sir,
I/We hereby give notice that the erection of the building on plot No Block No. . including execution and implementation of the energy conservation measures have been completed in accordance with the plans sanctioned vide your office communication No dated The following documents are enclosed
(i) A certificate of inspection on completion of the aforesaid building from S. Shri .Empanelled Energy Auditors (Building) vide Municipal Authority Order No. .dated .
The building is fit for use for which it has been erected/re-erected/constructed.
It is requested that permission to occupy or use the aforesaid building may be granted.
Yours faithfully,
Signature .
Name of the owner Plot No. block No. Address
Form X
[See Rule 5(7)]
[Certificate of Inspection by Empanelled Energy Auditors (Building) on review of completion of construction works enclosing construction documents and compliance forms in respect of Energy Conservation Building Code compliant building -Issue of certificate of compliance]
To
Name
Owner of the Building,
Address
Subject: Completion of Construction Works in respect of Energy Conservation Building Code compliant building
Certificate
I/We, .(Name(s)), being the authorised Empanelled Energy Auditors (Building)vide order No. .hereby state that I have verified the undertaking given by the owner, and have inspected the construction documents, compliance forms, check-lists, submitted on completion of building of the proposed Energy Conservation Building Code compliant building in the premises of plot No. .block No. .scheme .town/City .state of .and certify that the
(i) The works covered under the Energy Conservation Building Code Rules, 2018 have been completed to the best of my satisfaction. The details of the various components/system completed as per Energy Conservation Building Code Rules, 2018 are given below:
Name of the componentdated
1.
2.
3.
4.
5.
(ii) The energy performance index ratio of the said building match/with the data given in the aforesaid compliance documents specified in Para 1 above.
(iii) A list of the energy conservation measures deployed in the construction of aforesaid building enclosed. Necessary approvals required have been taken by the owner.
(iv) The building in my/our view meets the requirements of Energy Conservation Building Code Rules compliant building and is fit for occupancy for which it has been erected, Refer Rule 2(i).
(v) I further certify that all reasonable professional skill, care, and diligence have been taken in verifying the construction document and compliance forms in respect of the various elements of the components covered in the Energy Conservation Building Code Rules, 2018 and contents thereof are a true representation of the facts and meet the requirements of the Energy Conservation Building Code Rules, 2018.
(vi) The check-list duly completed, signed, sealed by the undersigned is enclosed.
Empanelled Energy Auditors (Building)
Seal/Name/Regd. Number/
Certification number
A copy of the certificate is sent herewith to:
(i) Commissioner, authority having jurisdiction, Town/City/State
(ii) Chief Executive, (By Name), State designated agency/Address/State of
Form XI
[See Rule 5(9)]
[Certificate of Inspection by Empanelled Energy Auditors (Building) on review of completion of construction works in respect of Energy Conservation Building Code compliant building-Communication of omissions and non-compliance to owner]
To
Shri .,
Address
Subject: Application for erection of Energy Conservation Building Code compliant Building in premises of plot no. .block No. scheme .street .name of the town/city-details of omission/non-compliance with the Energy Conservation Building Code Rules, 2018 on design/completion stage inspection.
Sir,
I/We, .(Name), being an authorised Empanelled Energy Auditors (Building)vide order No. .hereby state I/we have reviewed and verified the undertaking given by you and have inspected the construction documents, compliance forms, check-lists, submitted on completion of the proposed Energy Conservation Building Code compliant building in respect of the subject building and inform that the following omission/non-compliance have been found on inspection
(i)
(ii)
(iii)
(iv)
You are accordingly requested to take corrective action within a period of three months from the date of issue of this letter. Further action on your application for issue of Completion Certificate shall be taken after satisfactory compliance of the aforesaid omission/non-compliance.
Signature
Empanelled Energy Auditors (Building)
Registration number/Mobile number.
Form XII
[See Rule 5(12)]
Occupancy Certificate
(To be issued by Authority having jurisdiction in their occupancy certificate)
To
Name of the owner .
Address
Subject: Issue of Occupancy Certificate
Sir,
With reference to your notice of completion of an Energy Conservation Building Code compliant building construction dated on plot no .block no. situated at I/we hereby certify that the said building as per description annexed on plot No. .Block No. . Scheme . whose plans were sanctioned vide No dated has been inspected with reference to requirements of Energy Conservation Building Code Rules, 2018.
2. The building is declared fit for occupancy as follows:
Climate Zone24-Hour use Building/Regular Building Hospitals/Hotels/Call Centre/Other Building Types
Annexure
Description of the building
| Ground Floor |
Usage |
connected load |
| 1. 1st floor |
. |
. |
| 2. 2nd floor |
. |
. |
| 3. 3r floor |
. |
. |
| 4. 4th Floor |
. |
. |
| 5. etc. |
|
|
2. The energy performance index ratio of the building on the completion stage is as per the sanction plan. It has been decided by the authority having jurisdiction in consultation with the State designated agency that the building is declared fit for occupancy as specified above, subject to the condition that the owner shall undertake energy audit of the building and identify additional energy conservation measures to achieve the compliance with the energy performance index of the building approved in the sanctioned plan.
3. The energy performance of the Building shall be monitored and verified by the State Energy Conservation Building Code committee for the next two years.
Enclosures: copy of certified completion plan.
Yours faithfully,
(Signature of building official)
Authority having jurisdiction
Copy to
The Chief Executive, State designated agency
Form XIII
[See Rule 5(12)(ii)]
[Energy performance index Report Submission by Empanelled Energy Auditors (Building) to State designated agency after the building has become fully operational]
To
The Chief Executive,
State designated agency,
Government of (State)
Sub.: Energy performance index Report for Energy Conservation Building Code compliant building constructed on Plot no. .Block No. .Scheme .Street .Name of the town/city-Communication by the Empanelled Energy Auditors (Building)
Sir,
I/We, . (Name), being the authorised/Empanelled Energy Auditors (Building) vide order No. . hereby state that I/we have reviewed the undertaking given by the owner, energy consumption for year of the proposed building of type .in the premises of plot No. . Block No. .Scheme .Town/City . State of .and certify that the energy performance index ratio is which is less than or equal to one. The EPI report is enclosed.
I further certify that all reasonable professional skill, care, and diligence have been taken to verify the energy consumption of the aforesaid building.
Copies of the electricity bills have been enclosed for your reference.
Yours faithfully
Signature
Name of Authorized/
Empanelled Energy Auditors (Building)
Number/Mobile number
Seal
Enclosure: Energy performance index ratio report as specified in the Appendix D of the Code.
Copy to: Director, Buildings Programme, Bureau of Energy Efficiency, 4th Floor, Sewa Bhavan, R K Puram, New Delhi-110 066