Subpart 1.
IFC Table 1020.1.
IFC Table 1020.1 is amended as follows:
TABLE 1020.1
CORRIDOR FIRE-RESISTANCE RATING
| OCCUPANCY |
OCCUPANT LOAD SERVED BY CORRIDOR |
REQUIRED FIRE-RESISTANCE RATING (hours) |
| Without sprinkler system |
With sprinkler systemc |
| H-1, H-2, H-3 |
All |
Not permitted |
1 |
| H-4, H-5 |
Greater than 30 |
Not permitted |
1 |
| A, B, E, F, M, S, U |
Greater than 30 |
1 |
0 |
| R |
Greater than 10 |
1 |
0.5c/1d |
| I-2a |
All |
Not permitted |
0 |
| I-1, I-3 |
All |
Not permitted |
1b |
| I-4 |
All |
1 |
0 |
a For requirements for occupancies in Group I-2, see IBC Sections 407.2 and 407.3.
b For a reduction in the fire-resistance rating for occupancies in Group I-3, see IBC Section 408.8.
c Buildings equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1 or 903.3.1.2, where allowed.
d Group R-3 and R-4 buildings equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.3. See Section 903.2.8 for occupancies where automatic sprinkler systems are permitted in accordance with Section 903.3.1.3.