Table PSC 114.253 -1 [NESC Table 253-1, p. 225] Load factors for structures 1, crossarms, support hardware, guys, foundations, and anchors to be used with the strength factors of Table 261-1 (Changes)
(1) Change Footnote 2 to read:
2For guys and anchors associated with structures supporting communications conductors and cables only, this factor may be reduced to 1.33. For guys associated with structures supporting supply conductors or supply conductors and communications conductors and cables, this factor may be reduced to 1.5.
(2) Add Footnote 9 to read:
9For guys associated with structures supporting only supply conductors or supply conductors and communications conductors and cables, this factor may be reduced to 2.00.
(3) The reference to Footnote 9 is added to the value located at Transverse loads, Wind for Grade C, At crossings.
Wis. Admin. Code Public Service Commission § PSC 114.253
CR PSC 114.253(title) under s.
13.92(4) (b) 2, Stats., renum. (1) and (2) from PSC 114.253 -1 under s.
13.92(4) (b) 1, Stats., Register March 2015 No. 711, eff.4/1/2015.
Amended by, correction in PSC 114.253(title) under s.
13.92(4) (b) 2, Stats., Register June 2015 No. 714, eff.7/1/2015.
Amended by, CR 18-007: am. (intro.), (2) (intro.), (footnote), cr. (3) Register February 2020 No. 770, eff. 3/1/2020