The fire prevention rules for this state include, but are not limited to, the following:
Fire code. The State Fire Code includes:
101.1 Title. The words "[NAME OF JURISDICTION]" are replaced with "North Dakota".
102.1 Construction and design provisions. Subsection 3 does not apply.
102.4 Application of building code. Insert "as amended by the State of North Dakota" after the words "International Building Code" in both instances.
102.6 Historic buildings. Does not apply.
105.1.1 Permits required. The words "obtain the required permit" are replaced with "may be required to obtain a permit".
110.4 Violation penalties. Does not apply.
Fireworks, 1.4G. After "1507" insert "1 or otherwise listed and defined in North Dakota Century Code section 23-15-01".
[BG] Group E, day care facilities. The word "five" is replaced with "twelve".
[BG] Five or fewer children. The word "five" is replaced with "twelve" in both instances in this paragraph.
[BG] Five or fewer children in a dwelling unit. The word "five" is replaced with "twelve" in both instances in this paragraph.
[BG] Institutional Group I-4, day care facilities. The word "five" is replaced with "twelve".
Classification as Group E. The word "five" is replaced with "twelve".
[BG] Five or fewer occupants receiving care. The word "five" is replaced with "twelve" in both instances in this paragraph.
[BG] Five or fewer occupants receiving care in a dwelling unit. The word "five" is replaced with "twelve" in both instances in this paragraph.
[BG] Care facilities within a dwelling. The word "five" is replaced with "twelve" and the words "provided an automatic sprinkler system is installed in accordance with Section 903.3.1.3 or Section P2904 of the International Residential Code" are deleted.
308.1.4 Open-flame cooking devices. Exception 3. The words "2½ pounds [nominal 1 pound (0.454 kg) LP-gas capacity]" is replaced with "20 pounds (9.07 kg)".
308.1.3 Sky lanterns. Does not apply.
308.3 Group A occupancies. Exception 1. The following is added: "1.4 Open-flame devices for food warming."
510.1 Emergency responder radio coverage in new buildings. In the first sentence, replace "New" with "Where required by the fire code official, new".
The following is added:
"905.1.1 Standpipe hose. The installation of fire hose on standpipes may be omitted when approved by the fire code official. Approved standpipe hose valves and connections shall be provided where required."
907.2.10.2 Groups R-2, R-3, R-4, and I-1. The following subsection is added: "4. In dwelling units where the ceiling height of a room open to the hallway serving the sleeping rooms exceeds that of the hallway by twenty-four inches [610 mm] or more, smoke detectors must be installed in the hallway and in the adjacent room."
1010.1.9.4 Locks and Latches. The following is added:
1011.1 General. The following is added as an Exception:
"Stairways used only to attend equipment or private stairways serving an occupant load of ten or fewer persons and which are not accessible to the public need not comply with sections 1011 .2 through 1011.13."
1030.3. Maximum height from floor. The words "44 inches (1118 mm)" are replaced with "48 inches (1219.2 mm)".
6103.2.1.6 Use with self-contained torch assemblies. The words "2.7 pounds (1.2 kg)" are replaced with "12 pounds (5.44 kg)"
N.D. Admin Code 10-07-01-04
General Authority: NDCC 18-01-04, 18-01-33, 18-09-02, 23-15-03
Law Implemented: NDCC 18-01-02, 18-01-04, 18-01-33, 18-09-02, 23-15-03