Wis. Admin. Code PSC § 114.352 : Public Service Commission — Wisconsin State Electrical Code, Volume 1 — Omissions, Changes or Additions to NESC-2017 — Safety Rules for the Installation and Maintenance of Underground Electric Supply and Communication Lines —Buried Cable — Installation

Table PSC 114.352 -1 [NESC Table 352-1, p. 266] Supply cable, conductor, or duct burial depth (Change and Addition)

(1) Change the present "Exception" after the table to "Exception 1".
(2) Add a new Exception 2 as follows:
(3) (Addition) Add Note to read:

Wis. Admin. Code Public Service Commission § PSC 114.352

CR PSC 114.352(title) under s. 13.92(4) (b) 2, Stats., number (1) to (3) under s. 13.92(4) (b) 1, Stats., Register March 2015 No. 711, eff.4/1/2015.
Amended by, correction in (intro.) under s. 35.17, Stats., Register June 2015 No. 714, eff.7/1/2015.
Amended by, CR 18-007: am. (intro.) Register February 2020 No. 770, eff. 3/1/2020

Grounding and bonding conductors are covered by Rule 093.